Application Research of Detecting Transformer Windings’ Deformation Based on Vibration Frequency Response Analysis
|
SHAO Yuying1,XU Jian2,RAO Zhushi1,JIN Zhijian2,JIANG Yimin3,ZHOU Kai4
|
(1. State Key Laboratory of Mechanical System and Vibration, Shanghai Jiaotong University, Shanghai 200240, China; 2. Department of Electrical Engineering, Shanghai Jiaotong University, Shanghai 200240, China; 3. East China Grid Company Limited, Shanghai 200002, China;4.Shanghai Power Transformer Repairing and Testing Factory Co. Ltd, Shanghai 200435, China)
|
|
|
Abstract Vibration frequency response analysis (VFRA) was used to test the same winding under the same state at different times. The winding of phase C was artificially made faults of pressboard missing and winding radial deformation. The experimental data show that the VFRA can effectively detect the faults of windings’ deformation and the results are repetitive. Compared with shortcircuit reactance measurement, the VFRA is more sensitive.
|
Received: 13 January 2010
Published: 28 September 2010
|
|
|
|
|