Static Stability Analysis of Air-Conditioning Chilled Water System for Variable Differential Pressure Control Considering Bypass Loop Regulation Characteristics
|
LIU Xuefeng,LIU Jinping,CHEN Xinglong,LUO Wenhai |
(School of Electric Power; Key Laboratory of Efficient and Clean Energy Utilization of Guangdong Higher Education Institutes, South China University of Technology, Guangzhou 510641, China) |
|
|
Abstract The terminal cooling load distribution and pipe network structure of the air-conditioning system are the key factors that influence its control stability and reliability. An exact mathematical model of pipe network hydraulic characteristics was built in this paper based on a directreturn chilled water system, in which the regulation characteristics of bypass loop was considered in detail. The influence of pipe network hydraulic characteristics and energy consumption characteristics on pressure difference setting value of bypass loop were studied in detail, and the hydraulic characteristics in different running conditions were also studied. This paper focused on the influence of static stability and control quality on variable pressure difference control system by checkpoint of pressure difference feedback signal. The research shows that reasonable adjustment in control target value and setting value of bypass control valve are the key factors to achieve efficiency and stable operation.
|
Received: 23 September 2013
Published: 30 June 2014
|
|
|
|
|
[1] |
HUANG Yikun,CHEN Meishan,ZHANG Huisheng,WENG Shilie. Gas Path Diagnosis Based on Sigma Point Kalman Filter of Gas Turbine[J]. J. Shanghai Jiaotong Univ.(Sci.) , 2016, 50(04): 534-539. |
[2] |
JIA Hong,ZHANG Peng. Thermal Contraction Measurement of GFRP at Low Temperature[J]. J. Shanghai Jiaotong Univ.(Sci.) , 2016, 50(04): 502-505. |
[3] |
QUAN Rui-a, TANG Xin-Feng-a, QUAN Shu-Hai-b, c , HUANG Liang-b. Experimental Study on Automobile Exhaust Thermoelectric Generator in Series[J]. J. Shanghai Jiaotong Univ.(Sci.) , 2012, 46(05): 677-682. |
|
|
|
|