Characteristics of Conductor Dynamic Tension During Galloping for 500 kV Power Transmission Line with 6-Bundle |
YANG Xiaohui1,2,ZHANG Bo2,YANG Wei2,FU Zhengcai1 |
(1. Electric Department, Shanghai Jiaotong University, Shanghai 200030, China; 2. Electric Power Research Institute, Henan Electric Power Company,
Zhengzhou 450052, China) |
|
|
Abstract Taking the advantage and basic condition of comprehensive test centre built on real overhead transmission line (which belongs to State Grid Company of China), the conductor tension during galloping for 500 kV 6-bundle transmission line was measured and analyzed by using artificial airfoils with D shape on conductor, which had been proved to be quite essential for galloping excitation. Through the frequency spectrum comparison and the correlation analysis with wind load, the characteristics of conductor dynamic tension during galloping were obtained. It was shown that the conductor dynamic tension could be used as one of the critical parameters for galloping, which would not only be used for reliable analysis of tower-line system, but also be applied for the monitoring and identification of transmission line galloping. In a word, the characteristics of conductor dynamic tension during galloping are the basic data for the pre-warning of galloping and the performance evaluation of anti-galloping measuring.
|
Received: 27 July 2013
Published: 30 September 2014
|
|
|
|
|
[1] |
ZHU Lei, MA Dian-Guang, WANG Sheng-Yong, SHI Zhan-Guo, XIANG Chen, ZHANG Xiu-Bin. Control and Prevention of Ice Disasters in Power Grid with Power Supply Continuity [J]. J. Shanghai Jiaotong Univ.(Sci.) , 2012, 46(07): 1131-1137. |
[2] |
MA Yongquan,QIU Hongxing. A Novel Strategy for Controlling Wind-Induced Vibration of Large Span Transmission TowerLine System[J]. J. Shanghai Jiaotong Univ.(Sci.) , 2014, 48(12): 1751-1759. |
|
|
|
|